What is a pre-action system in the context of sprinkler systems?

A system that activates with smoke detection and a subsequent water release

A pre-action system is designed to provide an extra layer of protection before water is discharged from the sprinkler system. It operates using a two-step process: initially, a fire detection system, such as a smoke detector or heat detector, senses a potential fire condition and subsequently activates the pre-action valve. This valve allows water to fill the piping system while still requiring a second triggering event—typically the heat from a fire or manual activation through a pull station—for water to be released from the sprinklers themselves.

This dual-action approach significantly reduces the risk of accidental discharge caused by false alarms, making pre-action systems particularly suitable for environments where water damage might be as concerning as fire safety, such as in museums, data centers, or libraries. Therefore, the statement that describes a pre-action system as one that activates with smoke detection and a subsequent water release is accurate and effectively summarizes how these systems are engineered to function.